MODEL |
AP 5 |
AP 10 |
AP 20 |
Oil throughput |
500 l/h |
1000 l/h |
2000 l/h |
Max. oil content of transformer |
2 m³ |
4 m³ |
10 m³ |
Initial moisture content of oil |
50 ppm |
50 ppm |
50 ppm |
Residual moisture content after 1 pass |
approx. 5 ppm |
approx. 5 ppm |
approx. 5 ppm |
Residual moisture content after several passes |
approx. 3 ppm |
approx. 3 ppm |
approx. 3 ppm |
Initial gas content of oil |
10 Vol. % |
10 Vol. % |
10 Vol. % |
Residual gas content after 1 pass |
< 0,2 Vol. % |
< 0,2 Vol. % |
< 0,2 Vol. % |
Residual gas content after several passes |
< 0,1 Vol. % |
< 0,1 Vol. % |
< 0,1 Vol. % |
Heating capacity of indirect electrical heating |
10 kW |
20 kW |
40 kW |
Temperature difference at an inlet temp. of 20°C |
40 °C |
40 °C |
40 °C |
Oil temperature adjustable |
RT - 80 °C |
RT - 80 °C |
RT - 80 °C |
Pump speed of air cooled vacuum pump |
25 m³/h |
40 m³/h |
100 m³/h |
Ultimate vacuum approx. |
1 mbar |
1 mbar |
1 mbar |
Filter fineness approx. |
5/1 micron |
5/1 micron |
5/1 micron |
Connected load of equipment |
15 kVA |
25 kVA |
50 kVA |
|
|
|
|
Design: Movable (T): |
|
|
|
Length x Width x Height (mm) |
1200 x 900 x 1800 |
1350 x 900 x 1900 |
1650 x 1100 x 2200 |
Weight (kg) |
500 |
700 |
1200 |
Design: Mobile ( R): |
|
|
|
Height of rollers (mm) |
180 |
200 |
200 |
Design: Mobile on trailer (H): |
|
|
|
Casing with shaft (mm) |
2800 x 1600 x 2500 |
2800 x 1600 x 2500 |
3500 x 1900 x 3000 |
Admissible weight (kg) |
1300 |
1300 |
2000 |